FCQ5 series double electrical automatic conversion switch
View:12345 Page

FCQ5L-630 ~ 3200 appearance and installation dimensions shown in Figure 4 and Table 4

Controller panel Description
The controller’s LCD display instructions
        NA, NB, NC, is a commonly used power indicator: the RA, RB, RC, standby power indicator.
        Light indicates normal, off (flash) that the loss of phase;
        0A for the system failure, flashing alarm flashing alarm sound, the control mode of the "breaking" the key to artificially turn off the alarm sound.
        Controller mode description
        Manual key: artificial selection of commonly used power or standby power;
        Auto: use the power at that time into the automatic control state;
        Breaking: enable the load from the common power supply and standby power off. ○ (Set) (mobile) ○ (increase) (decrease) in the 4 button to set parameters, use enter a password. Did not enter the set parameters or password input state, a single press , ’s one of the key, not response. A new board is first powered up, and automatically generate the following default parameters:
        The default password: 9999
        The default conversion time:
        R-type (grid - grid): N-R15 seconds, R-N3 seconds
        F-type (grid - power generation): N-R15, R-N3 seconds (N is the commonly used power source; R is the standby power)
        63,100,225 breaking-R1 seconds, breaking-N1 seconds, N or R-breaking one second.
        400,630,800,1250 breaking-R2 seconds, breaking-N2, second N-or R-breaking 2 seconds.

View:12345 Page