FCQ5L-630 ~ 3200 appearance and installation dimensions shown in Figure 4 and Table 4
Controller panel Description The controller’s LCD display instructions NA, NB, NC, is a commonly used power indicator: the RA, RB, RC, standby power indicator. Light indicates normal, off (flash) that the loss of phase; 0A for the system failure, flashing alarm flashing alarm sound, the control mode of the "breaking" the key to artificially turn off the alarm sound. Controller mode description Manual key: artificial selection of commonly used power or standby power; Auto: use the power at that time into the automatic control state; Breaking: enable the load from the common power supply and standby power off. ○ (Set) ○ (mobile) ○ (increase) ○ (decrease) in the 4 button to set parameters, use ○ ○ ○ enter a password. Did not enter the set parameters or password input state, a single press ○, ○ ○ ’s one of the key, not response. A new board is first powered up, and automatically generate the following default parameters: The default password: 9999 The default conversion time: R-type (grid - grid): N-R15 seconds, R-N3 seconds F-type (grid - power generation): N-R15, R-N3 seconds (N is the commonly used power source; R is the standby power) 63,100,225 breaking-R1 seconds, breaking-N1 seconds, N or R-breaking one second. 400,630,800,1250 breaking-R2 seconds, breaking-N2, second N-or R-breaking 2 seconds.
|